logo

Detalles de los productos

Created with Pixso. En casa. Created with Pixso. Productos Created with Pixso.
ESPECIALMENTE regulador
Created with Pixso.

Ovation Ethernet Input Output Module Sequence Of Events 48V DC On Board 1C31233G04

Ovation Ethernet Input Output Module Sequence Of Events 48V DC On Board 1C31233G04

Nombre De La Marca: Westinghouse
Número De Modelo: 1C31233G04
Cuota De Producción: 1
Precio: Negotiations
Información detallada
Lugar de origen:
Reino Unido/Tailandia
categoría:
Módulo de fuente de alimentación redundante
Tipo:
Módulo de información digital
Detalles de empaquetado:
Nueva caja original
Resaltar:

Ovation Ethernet I/O module

,

48V DC sequence of events module

,

ESP controller input output module

Descripción del producto
Ovation Ethernet Input Output Module Sequence Of Events 48V DC On Board 1C31233G04
Ovation Module Sequence Of Events 48VDC On-board 1C31233G04 Digital I O Module Westinghouse
Item specifics
Brand: WESTINGHOUSE
Condition: New
Model: 1C31233G04
Shipping Weight: 2.45 lbs
Shipping Dimensions: 16.75 x 5.00 x 3.50 in
SKU: D645825 (GTK)
Category: PCB Circuit Boards
Quick detail
  • Brand: Westinghouse
  • Model: 1C31233G04
  • Country of origin: California, United States
  • Condition: New
  • Category: Redundant Power Supply Module
  • Type: Analog Input Electronic Module
Ovation Local I/O
The Ovation controller can directly support up to 16 independently driven branches of Ovation I/O. For local I/O, all modules reside in up to four standard cabinets, which are placed side by side. All field wiring leads to these cabinets.
Ovation Local I/O Specifications
Max branches per controller 16 branches
Max I/O modules per branch 8 modules
Max I/O modules per controller 128 modules
Max local I/O bus length 20m (60ft)
Ovation Redundant I/O
Redundant Ovation I/O modules are installed in the same fashion as standard Ovation I/O modules, but are associated in pairs located in adjacent branches.

The module pairs exchange health, status and I/O information via their personality module interconnections. This approach allows the user to take advantage of I/O redundancy by wiring the field terminations into a single terminal block on the primary I/O base, with no special control strategy configuration required.

Redundancy is applied at I/O configuration time, and during normal operation, the Ovation system automatically reads and compares the I/O channels of both modules and determines which value to use. When a fault is detected the system automatically switches to the backup module thus increasing reliability and availability of the process inputs or outputs.

Refer to the Ovation Redundant I/O Overview data sheet for complete details.
Remote I/O Specifications
Max. remote nodes 8 nodes
Max. I/O modules per node 64 (8 branches with 8 modules for each branch)
Max. I/O modules per controller 512 modules
Remote I/O bus configuration 10 BASE-FL Ethernet physical layer with a proprietary protocol
Remote I/O cycle time <100 microseconds (no repeaters)
Standard remote communications media Fiber optic
Maximum cable length for 850 nm fiber-optic media 4 km. Distances of 6 km can be achieved with repeaters (up to two repeaters)
Packaging & Shipping
  • We will ship the items within 3 working days after the payment is reached.
  • All the goods will be tested before shipment.
  • Packing in professional anti-static bag.
  • We can ship to you by DHL/TNT/UPS/EMS/Fedex... Pls contact us directly and we will ship as your requirement.